如前幾章所述,標準規(guī)定了保護裝置的大斷開時間,以避免人們接觸帶電部件的病理生理影響。對于間接接觸保護,應驗證斷路器在低于標準規(guī)定的大時間的時間內跳閘;通過比較待保護外露導電部分的小短路電流與標準規(guī)定時間對應的工作電流來進行驗證。當相與受保護導體上遠點處的保護導體之間短路時,出現(xiàn)小短路電流。對于小短路電流的計算,可以使用近似方法,假設:-由于短路電流引起的過熱,導體電阻相對于20°C值可以增加50%;-電源電壓降低80%視為短路電流的影響;-導線電抗僅適用于大于95 mm2的橫截面。通過在保護裝置和故障點之間應用歐姆定律,得出以下公式。公式符號和常數(shù)圖例:-0.8是表示電壓降低的系數(shù);-1.5是表示阻力增加的系數(shù);-Ur是相間的額定電壓;-U0是相與地之間的額定電壓;-S是相導體橫截面;-SN是中性導體橫截面;-SPE是保護導體橫截面;-ρ是20°C時的導體電阻率;-L是電纜的長度;-是總相導體橫截面(單相導體橫截面S乘以n,并聯(lián)導體數(shù)量)與保護導體橫截面SPE之間的比率,假設它們由相同的導體材料制成;-是總中性導體橫截面(單個中性導體橫截面SN乘以n,并聯(lián)導體數(shù)量)與保護導體橫截面SPE之間的比率,假設它們由相同的導體材料制成;-k1是考慮到橫截面大于95 mm2的電纜電抗的修正系數(shù),可從下表獲得:相導體橫截面[mm2]120 150 185 240 300 k1 0.90 0.85 0.80 0.75 0.72



As described in the previous chapters, the Standards give indications about the maximum disconnecting time for the protective devices, in order to avoid pathophysiological effects for people touching live parts. For the protection against indirect contact, it shall be verified that the circuitbreaker trips within a time lower than the maximum time stated by the Standard; this verification is carried out by comparing the minimum short-circuit current of the exposed conductive part to be protected with the operating current corresponding to the time stated by the Standard. The minimum short-circuit current occurs when there is a short-circuit between the phase and the protective conductors at the farthest point on the protected conductor. For the calculation of the minimum short-circuit current, an approximate method can be used, assuming that: - a 50 % increasing of the conductors resistance, with respect to the 20 °C value, is accepted, due to the overheating caused by the short-circuit current; - a 80 % reduction of the supply voltage is considered as effect of the short-circuit current; - the conductor reactance is considered only for cross sections larger than 95 mm2 . The formula below is obtained by applying Ohm’s law between the protective device and the fault point. Legend of the symbols and constants of the formula: - 0.8 is the coefficient representing the reduction of the voltage; - 1.5 is the coefficient representing the increasing in the resistance; - Ur is the rated voltage between phases; - U0 is the rated voltage between phase and ground; - S is the phase conductor cross section; - SN is the neutral conductor cross section; - SPE is the protection conductor cross section; - ρ is the conductor resistivity at 20 °C; - L is the length of the cable; - is the ratio between the total phase conductor cross section (single phase conductor cross section S multiplied by n, number of conductors in parallel) and the protective conductor cross section SPE assuming they are made of the same conductor material; - is the ratio between the total neutral conductor cross section (single neutral conductor cross section SN multiplied by n, number of conductors in parallel) and the protective conductor cross section SPE assuming they are made of the same conductor material; - k1 is the correction factor which takes into account the reactance of cables with cross section larger than 95 mm2 , obtainable from the following table: Phase conductor cross section [mm2 ] 120 150 185 240 300 k1 0.90 0.85 0.80 0.75 0.72
相關產品